Fire hydrant valve failure may result in corrosion damage

valve

IMCA has reported an incident in which a fire hydrant valve failed under pressure. The incident occurred during testing of the helideck firefighting system.

A hydrant valve assembly on the starboard side of the main deck failed under pressure. The 2kg valve assembly struck the deck head approximately 2 metres above, chipping paint on impact, and then fell to the deck below. No-one was injured. Whilst no one was in the immediate area, the impact was heard by several people. The force associated with the hydrant valve assembly failure had the potential to cause a significant injury or fatality.

Findings

  • There was an unexpected failure of the hydrant valve assembly studs. These studs were of type 303 Stainless Steel;
  • Expert analysis reveals that type 303 Stainless Steel is particularly susceptible to stress corrosion cracking (SCC) in a high ambient temperature (tropical environment);
  • The failure of the studs may have been accelerated by the presence of water surge, or water hammer, in the fire-fighting water system when activating the helideck firewater system;
  • Metallurgic analysis examined both “failed” and “non-failed” studs were provided by the vessel. The report stated that the cause of failure was chloride induced SCC, which is a common failure mode for austenitic stainless steels, including types 303, 304, and 316;
  • SCC failures commonly occur in tropical environments at ambient conditions for SS 303 and 304 grades, particularly for items under tensile stress and where the item has been cold worked. The report stated that all type 303 studs, regardless of exposure internally to raw seawater or externally to seawater spray would have eventually experienced complete fracture through SCC;
  • Equipment on vessels operating in tropical environments, exposed to relatively high environmental temperatures, will be exposed to increased risk of SCC. Austenitic stainless steels (grades 303 and 304 in particular) will fail from SCC in relatively short periods of time;
  • A contributing factor to the incident was the incorrect operation of the fire-fighting system inducing water surges or hammer into the fire main;
  • The root cause of this incident was the incorrect material specification of the studs for the environment and application.

Actions Taken

  • Careful consideration given to the increased likelihood of SCC in stainless steel for vessels operating extensively in tropical or high temperature environments, particularly for vessels designed and built in temperate climates;
  • All affected studs on fire hydrants to be replaced.

Source & Image credit: IMCA Safety Flash

Related Posts


Share on Facebook0Tweet about this on TwitterGoogle+0Share on LinkedIn6

Leave a Reply

Your email address will not be published. Required fields are marked *

*

Explore Our Group Sites:

The cookie settings on this website are set to "allow cookies" to give you the best browsing experience possible. If you continue to use this website without changing your cookie settings or you click "Accept" below then you are consenting to this. By continuing to use the site, you agree to the use of cookies. more information

The cookie settings on this website are set to "allow cookies" to give you the best browsing experience possible. If you continue to use this website without changing your cookie settings or you click "Accept" below then you are consenting to this. By continuing to use the site, you agree to the use of cookies.more information

Close